A detuned capacitor bank puts a reactor in series with each capacitor step so that the combination resonates below the lowest significant harmonic, usually at about 189 Hz for 7% detuning on a 50 Hz network. Above that frequency the step behaves inductively, so it cannot form a resonance with the supply at the 5th, 7th or higher harmonics. Al Qudrah Switchgear in Sharjah, UAE fits 7% detuned reactors wherever harmonics require them, and this article explains how to tell when that is.
Why harmonics and capacitors don't mix
A capacitor's impedance falls as frequency rises, so capacitors attract harmonic currents. Worse, a capacitor bank in parallel with the supply transformer forms a resonant circuit, and if that resonance falls near a harmonic present on the network, voltages and currents at that harmonic are amplified.
Non-linear loads produce the harmonics. Six-pulse variable speed drives, which run most chillers, pumps and fans in modern UAE buildings, generate mainly the 5th, 7th, 11th and 13th harmonics. UPS systems, LED drivers and IT loads add more, including the 3rd harmonic in the neutral.
The symptoms of a standard bank in a harmonic-rich network are familiar to anyone who has maintained one: capacitors swelling or failing early, fuses blowing for no visible reason, contactors burning, the bank running hot, and sometimes nuisance tripping elsewhere in the building.
How do you estimate the resonance frequency?
The parallel resonance order is roughly the square root of the network short-circuit power divided by the capacitor bank rating: h ≈ √(Ssc / Q). If h lands near 5, 7, 11 or 13, a standard bank is risky.
A worked example. A 1000 kVA transformer with 6% impedance gives a short-circuit power at the LV side of about 16.7 MVA, ignoring upstream impedance. With a 300 kvar bank fully switched in:
- Ssc / Q = 16,700 / 300 ≈ 56
- h ≈ √56 ≈ 7.5
The resonance sits between the 7th and 8th harmonic, close enough to the 7th to cause trouble if drives are present. And because an automatic bank switches steps in and out, the resonance moves as the regulator changes steps. At 150 kvar the same calculation gives about 10.5, near the 11th. A standard bank can pass through several dangerous points in a single day.
What does 7% detuning mean?
The percentage is the reactor's reactance as a share of the capacitor's reactance at 50 Hz. With p = 7%, the series tuning frequency is 50 / √0.07, which is about 189 Hz, or the 3.78th harmonic.
Below 189 Hz the step is capacitive and provides reactive power at 50 Hz, as it should. Above 189 Hz it is inductive, so it cannot resonate with the inductive supply at the 5th harmonic (250 Hz) or anything higher. The bank also stops soaking up harmonic current from the rest of the network, although it is not designed to act as a filter.
| Detuning factor | Tuning frequency (50 Hz) | Tuning order | Typical use |
|---|---|---|---|
| 5.67% | about 210 Hz | 4.2 | Low 3rd harmonic, 5th dominant |
| 7% | about 189 Hz | 3.78 | Most building and drive loads |
| 14% | about 134 Hz | 2.67 | Significant 3rd harmonic present |
For most UAE commercial and residential buildings, where the dominant harmonics come from drives, 7% is the usual choice. Where the 3rd harmonic is significant, for example on networks with heavy single-phase electronic loads, 14% may be needed. The decision should follow a measurement, not a habit.
Design details that change with detuning
Adding a reactor raises the voltage across the capacitor and changes the bank's output, so a detuned step is not just a standard step with a choke added. The capacitors, ratings and ventilation all change.
- Capacitor voltage. With 7% detuning the capacitor sees about 1 / (1 − 0.07), or 1.075 times, the system voltage at 50 Hz, plus the harmonic voltage. On a 415 V system, that means capacitors rated well above 415 V, typically 480 V class or higher depending on the manufacturer's matched selection.
- Output. The effective kvar of a detuned step at 415 V differs from the capacitor's nameplate rating. Manufacturers publish matched capacitor and reactor pairs for a given output; use those rather than mixing parts.
- Heat. Reactors add losses inside the panel. Detuned banks need more ventilation, and in UAE electrical rooms this is often the design limit.
- Reactor protection. Reactors carry a thermal switch that should trip the step if the reactor overheats.
When should you specify a detuned bank?
Specify detuning when non-linear loads make up a significant share of the total load, or when measurements at the MDB show voltage or current distortion high enough to threaten resonance. If in doubt, measure.
Our practical sequence:
- Look at the load schedule. If drives, UPS and LED lighting are a large share of the load, assume detuning is needed until shown otherwise.
- On existing sites, log harmonics at the MDB with a power analyser for several days, covering both peak and light-load periods.
- Run the resonance estimate for each switching state of the bank.
- Choose the detuning factor from the dominant harmonics, and select matched capacitors and reactors.
The IEC 61000 series sets the framework for harmonic emission and compatibility levels, and the utility may have its own limits at the point of connection. The consultant decides which apply. For the basics of sizing a bank, see Power factor correction with capacitor banks; for our standard and detuned panels, see capacitor banks.
Frequently asked questions
Does a detuned capacitor bank remove harmonics?
Not deliberately. A detuned bank is designed to avoid resonance and to protect itself from harmonic overload. Because its tuning frequency is below the 5th harmonic, it absorbs only a small amount of harmonic current. If the harmonic levels themselves must be reduced to meet a limit, you need a tuned filter or an active harmonic filter, which is a different design.
What is the tuning frequency of a 7% detuned bank?
On a 50 Hz network, the tuning frequency is 50 divided by the square root of 0.07, which is about 189 Hz, or the 3.78th harmonic order. That is safely below the 5th harmonic at 250 Hz, so the bank behaves inductively at the 5th, 7th and higher harmonics and cannot resonate with the supply at those frequencies.
When should I choose 14% detuning instead of 7%?
Choose 14% when the 3rd harmonic is significant at the point where the bank connects. A 7% bank tunes at about 189 Hz, which is close to the 3rd harmonic at 150 Hz. A 14% bank tunes at about 134 Hz, below the 3rd. A harmonic measurement at the MDB is the reliable way to decide.
Can I convert a standard capacitor bank to a detuned one?
Usually not by simply adding reactors. The existing capacitors are often rated for the system voltage only and would be overstressed by the voltage rise a reactor causes. The panel may also lack space and ventilation for reactors. In most cases the capacitors, and often the whole panel, need replacing with a matched detuned design.